10 Ton Water Cooled ChillerItem Features
•
Single Refrigerant Circuit
•
Copeland Scroll Compressors
with Advance Scroll Temperature Protection
• C&S Electric Contactors and Overload Relays
• Filter Drier
•
Danfoss
Thermostatic Expansion Valve
•
R410A
Refrigerant
- Non-Ozone Depleting
- Low Global Warming Impact
• Shell and Tube Type Evaporator
• Refrigerant High pressure gauge
• Refrigerant Low pressure gauge
•
Dual Pressure Switch
•
Water Flow Switch
• Stainless Steel (SUS304) Water Tank
• Multistage Centrifugal Pump
• Standard Stainless Steel (SUS304) NPT fittings
•
Emergency Stop Button
•
Interlock Switch
• Caster Wheels
•
Dual Purpose Siren/Beacon
Cooling Capacity
kcal/h
30200
BTU/h
120100
Nominal Tonnage
RT
10
Outlet Water Temp.
50
Condension Temp.
℉
104
Power Supply
3PH-460V-60HZ
Max Amp
A
26
Total Power Input
HP
12
Power Supply Cable Diameter
AWG 11
Safety Protection Device
Overload, Inverse Phase, High/Low Pressure, Water Flow, Water Level & Anti-Freeze Protection
Refrigerant
Type
R410A
Charge
Lbs
15
Compressor
Start Mode
Direct start
Type
Scroll Type
Qty
1
HP
10
RLA (Rated Load Amp)
22.0
LRA(Locked Rotor Amp)
125
Condenser
Type
tube and shell
Subcooling
℉
9
Heat Rejection
BTU/h
156633
Cooling Water flow
GPM
33
Water PressureDrop
PSI
7
Evaporator
Type
tube and shell
Superheat
℉
9
Heat Rejection
BTU/h
120119
Chilled Water Flow
GPM
27
Water PressureDrop
PSI
5
Energy Adjust Mode
100%-0%
Throttling Device
Mode
thermal expansion valve
Pipe
Chilled Water Inlet/Outlet
MNPT 2"
Cooling Water Inlet/Outlet
MNPT 2"
Water Pump
Flow
GPM
27
Head
PSI
55.1
LRA
A
14.4
Power
HP
2.0
Water Tank
Capacity
GAL
32
Sound Pressure
at 1 meter
DBA
65
Programming Controller
Display
LCD display
Controller
microcomputer controller
Temp Control Range
℉
41
℉
~95
℉
Temp Control Accuracy
℉
±3.6
℉
Dimensions
inches (LxWxH)
(For Reference)
51×25×57
Weight
lbs (For Reference)
706
Notes
• Cooling tons based on 10℃(50℉) chilled water outlet and 30℃(86℉) cooling water inlet.
• Chilled water work allowed temperature range: 5℃~35℃( 41℉ ~95℉ ).
• Chilled water in and out temperature difference: 3℃~8℃(5.4℉~14.4℉);
• Allowed ambient temperature range: -20℃~40℃(-4℉~104℉).
• Power supply: 3PH-460V-60HZ , Allowing the voltage fluctuate ±10%,
• A